Landis & Gyr LFL1.635 Burner Control

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Landis & Gyr LFL1.635 is an industrial burner safeguard controller for automatic ignition, burner sequence control and flame supervision. It belongs to the LFL1 Series and is designed for medium- to high-capacity forced-draft burners operating with gas, oil or dual fuel. The 220 V AC controller operates at 50-60 Hz and uses an electro-mechanical cam-drum mechanism to control the defined operating sequence, including checked air-damper operation.
Replacement commissioning requires more than matching the part number. The installed system must use the 220 V AC variant, a compatible LFL1 plug-in base with terminal connections, and a compatible flame detection arrangement. Flame supervision can use a QRA-series UV detector, an ionization probe or a flame rod. Before energising a spare, verify the burner sequence, detector arrangement, supply voltage, fuse ratings and plug-in base configuration against the existing burner panel. The identical LFL1.635 designation is also associated with Siemens branding.
The front-cover position indicator disk shows the active operating-program step and lockout position, giving service technicians a visual reference during commissioning and troubleshooting. First-line checks include the supply voltage, fuse condition, burner sequence timing, flame detector or flame rod connection and plug-in base connections. The LFL1.635 is discontinued under the Landis & Gyr branding, so an exact replacement or tested exchange unit should be matched to the installed burner system before return to service.
Technical Specifications
| Manufacturer | Landis & Gyr |
| Part number | LFL1.635 |
| Model/type | Burner Control |
| Component type | Industrial burner safeguard controller |
| Product family | LFL1 Series |
| Supply voltage | 220 (-15%/+10%) V AC |
| Supply frequency | 50-60 Hz, ±6% |
| Power consumption | 3.5 VA |
| Pre-purge time | 66-67.5 s |
| Safety time | 2.5 maximum; 5 variant |
| Internal fuse rating | 6.3 A slow-blow |
| Maximum external fuse rating | 10 A slow-blow |
| Flame detection interface | UV detector or ionization probe/flame rod |
| Mounting and connection | Plug-in base required; ordered separately |
| Program sequence mechanism | Electro-mechanical cam drum |
| Lifecycle status | Discontinued under Landis & Gyr branding; identical designation continued by Siemens |
Communication and System Integration
The LFL1.635 uses a dedicated plug-in base with terminal connections for integration into the burner control panel. The plug-in base is required and is ordered separately, so its arrangement must match the installed LFL1 system before a replacement is commissioned.
Flame supervision is connected through a compatible QRA-series UV detector or through an ionization probe or flame rod. The controller supports gas, oil and dual-fuel forced-draft burner systems with checked air-damper control. Confirm the installed detector type and terminal connections before transferring the controller into service.
Diagnostics and Status Indication
A position indicator disk on the front cover shows the current operating-program sequence step and the lockout position. This provides a visual indication of the controller position during burner commissioning and service.
For troubleshooting, inspect the 220 V AC supply, the 6.3 A internal slow-blow fuse, the maximum 10 A slow-blow external fuse, burner sequence timing, flame detector or flame rod connections and the plug-in base terminals. Verify that the installed UV detector or ionization arrangement is compatible with the LFL1.635.
Replacement and Spare Part Considerations
Match the replacement to the Landis & Gyr LFL1.635 part number, the 220 V AC supply variant, the LFL1 plug-in base and the installed burner sequence. The burner may use a QRA-series UV detector, an ionization probe or a flame rod, and this flame detection arrangement must be compatible with the replacement controller.
The LFL1.635 is discontinued under the Landis & Gyr name and the identical designation continued under Siemens branding. When sourcing a Siemens-branded replacement, compare the designation, supply voltage, sequence timing, detector connection and plug-in base arrangement with the installed unit.
After installation, check the supply and fuse condition, confirm the burner sequence and pre-purge timing, inspect the flame detection connections and use the front position indicator to identify the operating step or lockout position during commissioning.
Frequently Asked Questions
What is the Landis & Gyr LFL1.635 used for?
The LFL1.635 is an industrial burner safeguard controller for automatic ignition, burner sequence control and flame supervision on medium- to high-capacity gas, oil and dual-fuel forced-draft burners.
What supply does the LFL1.635 require?
The LFL1.635 is specified for 220 V AC with a -15%/+10% voltage tolerance and 50-60 Hz operation with ±6% frequency tolerance.
Which flame detectors are compatible with the LFL1.635?
Flame supervision can use a compatible QRA-series UV detector, an ionization probe or a flame rod.
Is the plug-in base included with the LFL1.635 burner control?
The LFL1.635 requires a dedicated plug-in base with terminal connections, and the plug-in base is ordered separately.
How can the LFL1.635 operating state be checked?
The front-cover position indicator disk shows the operating-program sequence step and lockout position. Service checks also include the supply voltage, fuse condition, burner sequence timing, flame detection connections and plug-in base connections.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.
Disclaimer:
We are not an authorised distributor of Landis & Gyr.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.