Vacon NXP00725A5H1SSSANA3000000 45 kW NXP Drive

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Vacon NXP00725A5H1SSSANA3000000 is a VACON NXP NXP Drive frequency inverter for variable-speed control of three-phase industrial motors. This air-cooled FR7 drive accepts a 380-500 V AC, 3-phase supply at 45-66 Hz and provides 72 A low-overload current for applications up to 45 kW at 400 V. For high-overload operation, it provides 61 A and 37 kW at 400 V. The drive supports U/f frequency control, open-loop sensorless vector control and closed-loop vector control, with an output-frequency range of 0-320 Hz and IP54 / NEMA 12 protection.
Replacement commissioning depends on the installed configuration. The drive has five option slots, A, B, C, D and E; this unit includes an OPTA1 control board in Slot A and an OPTA3 option board in Slot C. OPTA1 provides 6 digital inputs, 2 analog inputs, 1 analog output, 2 relay outputs and 1 digital output, while OPTA3 provides 1 relay output, 1 digital output and 1 thermistor input. The included graphic display keypad supports direct plug-in or remote mounting, local control, parameter backup and restoration, alarm-history review and fault-code review. VACON All-in-One application packages and customizable applications created with VACON System Builder may require configuration and application transfer before the spare can operate in the machine.
The VACON NXP platform supports communication expansion through compatible option cards for Modbus RTU, PROFINET, PROFIBUS-DP, EtherNet/IP, EtherCAT and CANopen. Commissioning and troubleshooting can be performed through the keypad or fieldbus, while VACON NCDrive provides online monitoring, parameterization, an oscilloscope and a data logger. When replacing this discontinued legacy product, check the FR7 frame size, IP54 / NEMA 12 protection, installed option-board arrangement, application, parameters and firmware compatibility. Faults involving internal hardware, memory or control-board operation may require repair or exchange of the drive.
Technical Specifications
| Manufacturer | Vacon |
| Part number | NXP00725A5H1SSSANA3000000 |
| Model/type | NXP Drive |
| Component type | Frequency inverter drive |
| Product family | VACON NXP |
| Input voltage | 380-500 V AC, 3-phase |
| Input frequency | 45-66 Hz |
| Low-overload rated current | 72 A |
| High-overload rated current | 61 A |
| Low-overload rated power | 45 kW at 400 V |
| High-overload rated power | 37 kW at 400 V |
| Output frequency | 0-320 Hz |
| Switching frequency | 3.6 kHz default, adjustable 1-6 kHz |
| Control methods | U/f frequency control; open-loop sensorless vector control; closed-loop vector control |
| Frame size | FR7 |
| Protection rating | IP54 / NEMA 12 |
| Option slot architecture | Five option slots: A, B, C, D and E |
| Installed control board | OPTA1 in Slot A with 6 digital inputs, 2 analog inputs, 1 analog output, 2 relay outputs and 1 digital output |
| Installed option board | OPTA3 in Slot C with 1 relay output, 1 digital output and 1 thermistor input |
| Operator interface | Included graphic display keypad with direct-plugin and remote-mounting capability |
| Optional communication protocols | Modbus RTU, PROFINET, PROFIBUS-DP, EtherNet/IP, EtherCAT and CANopen via expansion cards |
| Application software | VACON All-in-One application packages and customizable software through VACON System Builder |
| Lifecycle status | Discontinued legacy product |
Programming and Configuration
The VACON NXP platform supports VACON All-in-One application packages and customizable software created with VACON System Builder. The included graphic keypad provides parameter backup and restoration, allowing drive settings to be transferred when preparing a replacement.
VACON NCDrive supports commissioning, parameterization and online monitoring. Its oscilloscope and data logger assist with troubleshooting and reviewing drive behaviour. Before commissioning a spare, transfer the required parameters and application configuration, then confirm the installed OPTA1 and OPTA3 boards match the machine configuration.
The graphic keypad can be used for local control and fault-code review, or the drive can be parameterized and troubleshot through the fieldbus. Application, parameter and firmware compatibility should be checked as part of replacement commissioning.
Communication and System Integration
The Vacon NXP00725A5H1SSSANA3000000 provides five option slots, A through E, for expansion with I/O, encoder, fieldbus and safety modules. The installed OPTA1 control board is in Slot A, and the installed OPTA3 option board is in Slot C.
OPTA1 provides 6 digital inputs, 2 analog inputs, 1 analog output, 2 relay outputs and 1 digital output. OPTA3 adds 1 relay output, 1 digital output and 1 thermistor input. These installed boards are important matching points when selecting a replacement drive.
Compatible expansion cards support Modbus RTU, PROFINET, PROFIBUS-DP, EtherNet/IP, EtherCAT and CANopen. Fieldbus parameterization and troubleshooting are available alongside the graphic keypad interface and VACON NCDrive.
Diagnostics and Status Indication
The included graphic keypad displays alarms, stores fault history and supports fault-code review. Active fault-trip diagnostics identify drive conditions requiring attention, while parameterization and troubleshooting can be carried out through the keypad interface or fieldbus.
VACON NCDrive adds online monitoring, an oscilloscope and a data logger for commissioning and fault investigation. First-line checks should follow the displayed fault: inspect motor load, motor cables, supply voltage, cooling, option-board seating, fieldbus connections and external fault circuits where applicable. Internal control-board, memory and hardware faults may require repair or replacement of the drive.
The fault-code list below covers drive conditions including overcurrent, DC-bus voltage faults, phase supervision, temperature faults, communication faults and option-slot faults.
Replacement and Spare Part Considerations
For a direct replacement, match the complete part number NXP00725A5H1SSSANA3000000 and confirm the FR7 frame size, IP54 / NEMA 12 protection, 380-500 V AC, 3-phase input and 72 A low-overload or 61 A high-overload rating required by the machine. The 45 kW low-overload and 37 kW high-overload ratings apply at 400 V.
The installed option-board arrangement is a key compatibility point: OPTA1 is fitted in Slot A and OPTA3 in Slot C. Check the required I/O, thermistor connection, fieldbus card and other Slot A-E functions before installing a spare. Optional communication protocols use expansion cards and should match the control architecture.
A spare may require parameter restoration, application transfer and commissioning through the graphic keypad, fieldbus or VACON NCDrive. Confirm VACON All-in-One or VACON System Builder application compatibility, firmware alignment and keypad configuration before returning the machine to service. For internal hardware, memory or control-board faults, ABC Industrial Parts can support repair or exchange preparation.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| F1 | Overcurrent | Drive detected abnormally high output current. | Sudden heavy load increase, motor cable short circuit or unsuitable motor power. | Check motor load, motor-cable insulation and acceleration ramps. |
| F2 | Overvoltage | DC bus voltage exceeded the internal threshold. | Deceleration time too short, high overhauling load or input mains spike. | Increase deceleration time, fit a brake resistor and check supply voltage. |
| F3 | Earth Fault | Output phase-current imbalance indicates an earth fault. | Insulation failure in the motor or motor cable. | Check motor and motor-cable insulation resistance. |
| F8 | System Fault | Internal component or hardware failure detected during operation. | Control-board malfunction, component fault or internal memory corruption. | Power cycle the drive; if the fault persists, return the unit for repair. |
| F9 | Undervoltage | DC bus voltage fell below the minimum operating threshold. | Mains voltage loss, power-supply brownout or blown input fuse. | Check supply voltage, input fuses and the mains contactor. |
| F11 | Output Phase Supervision | Current measurement indicates a missing output phase. | Disconnected motor cable, open motor winding or opened contactor. | Check motor connection, output cable and motor contacts. |
| F13 | Drive Under-temperature | Heatsink temperature is below the minimum allowable value of -10 °C. | Ambient temperature is too low. | Keep the operating ambient temperature within specification. |
| F14 | Drive Over-temperature | Heatsink temperature exceeded the maximum safety limit. | Cooling-fan failure, blocked heatsink or excessive ambient temperature. | Check the cooling fan, clean the heatsink and verify enclosure ventilation. |
| F15 | Motor Stalled | Motor is operating in the stall region. | Excessive mechanical load or mechanical blockage. | Check the mechanical load and motor-shaft rotation. |
| F16 | Motor Over-temperature | Motor thermal model indicates overheating. | Motor overload or low-speed operation without forced cooling. | Reduce motor load and check thermal-model settings. |
| F17 | Motor Underload | Motor current dropped below the underload-limit curve. | Broken belt or uncoupled load. | Check the mechanical transmission and coupling. |
| F24 | Microprocessor Watchdog Fault | Control-board microprocessor watchdog was triggered. | Internal microcode or hardware crash, or severe electrical noise. | Check grounding and EMC, power cycle the unit, and return it for service if unresolved. |
| F25 | Microprocessor Bus Fault | Internal communication bus error occurred between drive control circuits. | Hardware-board defect or corrupted memory access. | Repair or replace the drive. |
| F26 | Startup Error | Drive startup diagnostic sequence failed. | Faulty option board, corrupted configuration file or internal power-supply error. | Check option-board mounting and return the drive for repair if the error persists. |
| F29 | Thermistor Fault | Thermistor input detected an open or short circuit. | Broken motor-thermistor cable or overheated motor. | Check thermistor wiring and motor temperature. |
| F31 | IGBT Temperature Fault | Calculated or measured IGBT junction temperature is too high. | Severe short-term current overload or cooling-fan failure. | Check acceleration time, load and cooling-fan operation. |
| F32 | Fan Cooling Fault | Cooling-fan feedback monitor indicates fan failure. | Cooling fan is blocked or disconnected. | Check or replace the internal cooling-fan unit. |
| F50 | Analog Input Signal Loss | The 4-20 mA analog-input signal dropped below 4 mA. | Broken analog-signal cable or transmitter failure. | Inspect the analog-input cable and signal source. |
| F51 | External Fault | A fault signal was received on a digital input configured for external fault. | External protective relay or safety device has tripped. | Inspect the external circuit connected to the fault input. |
| F52 | Keypad Communication Error | Control board lost serial communication with the keypad. | Keypad cable is disconnected or damaged. | Check the keypad connection and cable. |
| F53 | Fieldbus Fault | Data connection was lost between the drive and fieldbus master. | Disconnected fieldbus cable, network timeout or stopped PLC. | Check network cabling, bus-master state and communication parameters. |
| F54 | Slot Fault | Option-board slot communication failed or the option board was not recognised. | Option card is loose or defective. | Reseat or replace the option card in the affected slot. |
Frequently Asked Questions
What is the exact replacement part number for this Vacon drive?
The exact part number is NXP00725A5H1SSSANA3000000. It is a Vacon VACON NXP NXP Drive frequency inverter with an FR7 frame and IP54 / NEMA 12 protection.
What motor ratings does the Vacon NXP00725A5H1SSSANA3000000 support?
At 400 V, the drive provides 45 kW and 72 A for low-overload operation, or 37 kW and 61 A for high-overload operation.
Which control methods are available?
The drive supports U/f frequency control, open-loop sensorless vector control and closed-loop vector control.
Which communication protocols can be used with the VACON NXP platform?
Compatible expansion cards support Modbus RTU, PROFINET, PROFIBUS-DP, EtherNet/IP, EtherCAT and CANopen.
What should be transferred when commissioning a replacement drive?
Transfer the required parameters and application configuration using the graphic keypad, fieldbus or VACON NCDrive. Check VACON All-in-One or VACON System Builder compatibility, firmware alignment and the installed option-board configuration.
What should be checked for an F53 Fieldbus Fault?
Check the network cabling, the fieldbus master's state and the communication parameters. F53 indicates that the data connection between the drive and fieldbus master was lost.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.
Disclaimer:
We are not an authorised distributor of Vacon.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.